3-phase Voltage Transformers
Detailed Product Description
Technical Parameters for JSQXF2-126 Voltage Transformers
1 Rated primary voltage: 66kV, 110kV, 132kV and 220kV and so on.
2 Rated secondary voltage: 0.1 /√3kV or 0.11 /√3kV.
3 Rated voltage of residual voltage winding: 0.1kV or 0.11kV.
4 Rated frequency and number of phases: 50Hz or 60Hz 3-phase.
5 Voltage ratio, maximum rated output and corresponding accuracy class please see table 1.
Table 1 Voltage Ratio, Maximum Rated Output and Corresponding Accuracy Class Table
Voltage Ratio (kV) | Accuracy Class and Rated Output (VA) | ||||
Secondary 1a-1n | Secondary 2a-2n | Residual da-dn | |||
0.2 | 0.5 | 0.2 | 0.5 | 3P | |
66 /√3/ 0.1 /√3-0.1 /√3-0.1 110 /√3/ 0.1 /√3-0.1 /√3-0.1 132 /√3/ 0.1 /√3-0.1 /√3-0.1 or 220 /√3/ 0.1 /√3-0.1 /√3-0.1 | 75 | 75 | 300 | ||
75 | 100 | ||||
200 | |||||
150 | 150 | ||||
300 |
6 Thermal limit output: 1500VA (for each secondary winding).
7 Except for limit loaded power factor from 0.8 (lag) to 1, the rest loaded power factor is 0.8 (lag).
8 Rated voltage factor and corresponding rated duration: 1.2 continuous, 1.5 30 s.
9 Rated pressure of SF6 (20): 0.40 ~ 0.58 MPa.
10 Minimum operating pressure of SF6 (20): 0.35 ~ 0.50 MPa.
Note: Those listed in the table above are the routine parameters, if there is any different parameter required, we can design according to the technical parameters of the clients.