Dry-type Current Transformers
Detailed Product Description
1 Possessing those advantages of light structure, oil-free, gas-free, porcelain-free, fire-proof and explosion-proof etc, it has been serviced in current measurement and relay protection in power system with the rated voltage of 35 kV.
2 Technical Parameters for LGB-35W (1~3) Current Transformers
2.1 Rated voltage 35 kV
2.2 Highest voltage for equipment 40.5 kV
2.3 Rated primary current 50 A~4000 A
2.4 Rated secondary current 5 A or 1A
2.5 Rated frequency 50 (60) Hz
2.6 Rated output
20~40VA (If any other rated output required, We can satisfy it.)
2.7 Accuracy class and accuracy classes combination
Steady accuracy classes are 0.2S, 0.2, 0.5S, 0.5, 5P, 10P, PR and PX; transient accuracy classes are TPS, TPX, TPY and TPZ. There are 1~6 pcs secondary windings in a CT.
2.8 Instrument security factor (FS) of measuring class 5 or 10
2.9 Accuracy limit factor (ALF) of protective class 5, 10, 15, 20, 30 or 40
2.10 Rated continuous thermal current Icth 1.2In
2.11 For rated short-time thermal current Ith (rms) and rated dynamic current Idyn (peak), please see Table 1
Table 1
Primary Current (A) | 50~150 | 200~300 | 400~600 | 800~1500 | 2000~4000 |
Rated Short-time Thermal Current (rms) (kA) | 10.5 | 21 | 42 | 84 | 108 |
Rated Dynamic Current (Peak) (kA) | 26.3 | 52.5 | 105 | 210 | 270 |
2.12 Arcing distance ≥410 (mm)
2.13 Creepage distance of outer insulation please see Table 2
Table 2
Pollution Protection Class | Class II (W1) | Class III (W2) | Class IV (W3) |
Creepage Distancemm | ≥810 | ≥1013 | ≥1256 |