SF6 Current Transformers

SF6 Current Transformers
Product Detailed
Related Categories:Transformers

Detailed Product Description


Technical Parameters for LVQB3-110W(1~3) Current Transformers

1  Rated voltage  110 kV

2 Highest voltage for equipment  126 kV

3 Rated primary current  100 A~4000 A

4 Rated secondary current  5 A or 1 A

5 Rated frequency  50 (60) Hz

6 Rated output  20~50 VA  (If any other rated output required, We can satisfy it.)

7 Accuracy class and accuracy classes combination

Steady accuracy classes are 0.2S, 0.2, 0.5S, 0.5, 5P, 10P, PR and PX; transient accuracy classes are TPS, TPX, TPY and TPZ. There are 1~6 pcs secondary windings in a CT. 

8 Rated operating pressure of the gas SF6 is  0.40 MPa

9 Minimun operating pressure of the gas SF6 is  0.35 MPa

10 Instrument security factor (FS) of measuring class  5 or 10

11 Accuracy limit factor (ALF) of protective class  5, 10, 15, 20 or 30 

12 Rated continuous thermal current Icth  1.2In

13 For rated short-time thermal current Ith(rms) and rated dynamic current Idyn (peak), please see Table 1.

Table 1

Primary Current (A)

100~250

300~800

1000~2500

3000~4000

Rated Short-time Thermal Current (rms)

(kA), 3s

21

31.5

42

50

Rated Dynamic Current (Peak) (kA)

52.5

80

105

125

14 Arcing distance ≥1010 mm

15 Creepage distance of outer insulation please see Table 2

Table 2

Pollution Protection Class

Class II (W1)

Class III (W2)

Class IV (W3)

Creepage Distancemm

≥2520

≥3150

≥3906